Part #462888
Modular Small Cabinet Fan
®
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Model MSCF-BI
Model MSCF-FC
General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
2. The rotation of the wheel is critical. It must be
free to rotate without striking or rubbing any
stationary objects.
3. Motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than the maximum
cataloged fan rpm. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked
to make sure it is not exceeding the motor
nameplate amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces,
or chemicals. Replace cord immediately if
damaged.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC), the
National Fire Protection Agency (NFPA), where
applicable. Follow the Canadian Electric Code
(CEC) in Canada.
6. Verify that the power source is compatible with
the equipment.
DANGER
7. Never open blower access doors while the fan is
running.
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Model MSCF Modular Small Cabinet Fan
1
®
Table of Contents
Installation
Installation
Unit Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mounting / Hanging Instructions . . . . . . . . . . . . . 4
Mounting Dimensions. . . . . . . . . . . . . . . . . . . . . . 5
Dimensions / Weights. . . . . . . . . . . . . . . . . . . . . . 6
Filter Sizes / Quantity . . . . . . . . . . . . . . . . . . . . . . 6
Coil Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .7-9
Start-Up
Electric Heater. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Operation
Electric Heater. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance
Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Drain Pan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Reference
Start-Up Documentation. . . . . . . . . . . . . . . . . . . 17
Maintenance Log . . . . . . . . . . . . . . . . . . . . . .18-19
Warranty . . . . . . . . . . . . . . . . . . . . . . . . .Backcover
System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . 10
Troubleshooting
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Motor Overamps . . . . . . . . . . . . . . . . . . . . . . . . . 10
Insufficient / Too Much Airflow. . . . . . . . . . . . . . 10
Excessive Noise or Vibration . . . . . . . . . . . . . . . 10
Start-Up
Coil Module . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
Drain Pan / Drain Trap . . . . . . . . . . . . . . . . . . . . 13
Unit Layout
Airflow
4
7
2
8
8
8
8
8
6
8
5
3
9
1
1. Fan and Cabinet Section
6. Mixing Box Section
7. Lifting Lugs
2. Cooling Section
• Chilled Water
• DX Coils
Four (4) lifting lugs for each section
8. Side Access Panels
3. Heating Section
• Hot Water
Right and left access to each section
(image shows panels removed)
• Steam Coils
9. 7/8-inch knockout is provided for the
recommended electrical wiring penetration or
disconnect switch.
4. Filter Section
Filter may be mounted in Mixing Box Section
5. Plenum Section
Model MSCF Modular Small Cabinet Fan
3
®
Mounting Instructions
Hanging Instructions
Greenheck’s Modular Small Cabinet Fan (MSCF)
should be lifted by the factory supplied lifting lugs
(see Figure 1) or frame rails and a spreader bar
(see Figure 2) to prevent damage from occurring to
the equipment. Avoid twisting or uneven lifting of
equipment. Do not lift equipment by coil connections
or headers. The unit must remain upright during lifting.
All access doors and panels must be closed during
lifting to avoid damage.
The MSCF should be hung by the factory supplied
lifting lugs or field supplied frame rails as shown
respectively in Figures 3 and 4. The number of
hanging brackets used will be determined by the
number of fan modules.
Spreader Bar
Figure 3
Lifting lugs
Figure 1
Figure 4
Spreader Bar
External Mounting Isolation
The MSCF is available with external neoprene or
spring isolation options. When external isolation is
selected, a bridge bracket will be provided to reduce
installation time (see Figure 5).
3/8-16x3/4 Spinlock Bolt
Two required per assembly
3/4 inch Flat Washer
One per assembly as needed
3/8-16 Spinlock Nut
Two required per assembly
Bridge Bracket
Part No. 711779
Drawing No. 89814
One required per assembly
Frame Rails
(by others)
Hanging Bracket
Part No. 710774
Drawing No. 85537
Hanging Bracket
Part No. 710774
Figure 2
Drawing No. 85537
3/8-16x3/4 Spinlock Bolt
Two required per assembly
HANGING ASSEMBLY
Bridge Bracket
Part No. 711779
Drawing No. 89814
One required per assembly
3.0 inch
3/4 inch Flat Washer
One required per assembly
Figure 5
3/8-16 Spinlock Nut
Two required per assembly
BASE ASSEMBLY
Model MSCF Modular Small Cabinet Fan
4
®
Modular Construction
The MSCF is designed to be modular so it can be
mounted as an assembly or as individual sections
when the appropriate lifting equipment is not
available.
MSCF Mounting Dimensions
K
J
L
F
A
B
C
D
E
G
H
M
Mixing
Box
24 in.
Plenum
12 in.
Plenum
Filter
*Heating
Cooling / Combo
Coil
Fan
Horizontal Hanging
E
A
D
Unit
Size
B
C
F
G
H
J
K
L
M
w/o
w/
Hot Water 4 Row HW
Vertical Sloped
Filter Filter
1 & 2 Row & Steam
15
20
25
30
45
50
65
85
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
18.5 18.5 6.75
18.5 18.5 6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
18.5
18.5
21
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
18.5
18.5
18.5
18.5
18.5
18.5
18.5
18.5
19
19
23
26
26
32
36
36
38
38
38
38
50
50
50
62
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3
3
3
3
3
3
3
3
.5
.5
.5
.5
.5
.5
.5
.5
43
43
43
43
55
55
55
67
21
25
26
26
32
32
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
25
26
26
28
28
*See CAPS for electric heating dimensions.
All dimensions are in inches.